SLCC-A - Condensate Corrosion Inhibitor

Rate this item
(3 votes)
BOILER WATER TREATMENT
www.ship-service.ru

SLCC-A - Condensate Corrosion Inhibitor

Description

SLCC-A condensate corrosion inhibitor is a liquid alkaline amine used to control corrosion in condensate return lines and on steam condensing surfaces by traveling and condensing with the steam. SLCC-A inhibitor neutralizes the corrosive effects of carbonic acid formed by carbon dioxide and maintains noncorrosive pH conditions from the point of condensation onward throughout the system. SLCC-A corrosion inhibitor is used in our standard boiler water treatment programs for low-pressure boiler systems (0-32 bar) and medium-pressure steam propulsion vessels (32-60 bar). It is also used in our ULTRAMARINESM boiler water treatment program for high-pressure steam generating systems (60-84 bar).

SLCC-A condensate corrosion inhibitor is NSF registered as a nonfood compound under category G6, a water treatment product used in boiler steam lines for food contact in food processing establishments. It is also registered under category G7, a water treatment product used in boiler steam line for nonfood contact in food processing establishments.

Application

Dosage, Testing and Control: Continuously dose SLCC-A condensate corrosion inhibitor to maintain condensate pH within the specified range. Slug dosing may result in erratic pH conditions and/or triggering of false condensate salinity alarm. The daily condensate pH test result determines the necessary dosage. For details on the testing procedure, refer to the appropriate control and dosage chart, or contact your local Drew Marine representative. Feed Points: For low-pressure boiler systems, continuously dose SLCC-A corrosion inhibitor with diluted AMERZINE corrosion inhibitor or diluted DREWPLEX OX corrosion inhibitor using a common DREW™ beta metering system to the feedwater line downstream of the feedwater recirculation offtake. If there is no feedwater recirculation, dose continuously to the feed pump suction. For medium- and high-pressure boiler systems, continuously dose diluted SLCC-A corrosion inhibitor with diluted AMERZINE corrosion inhibitor or diluted DREWPLEX OX corrosion inhibitor using a common DREW beta metering system to the deaerator storage section or suction side of the feed pump.

Typical Physical Properties

Appearance: Slightly hazy liquid

pH: 11.4

Specific Gravity at 25° C (77° F): 1.0

Odor: Slightly ammoniacal

Packaging

SLCC-A condensate corrosion inhibitor is available in 25- liter

Containers

Important Information

Ashland maintains Material Safety Data Sheets on all of its products. Material Safety Data Sheets contain health and safety information for your development of appropriate product handling procedures to protect your employees and customers.

Our Material Safety Data Sheets should be read and understood by all of your supervisory personnel and employees before using Ashland products in your facilities.